Full Load Current in
Amperes - Three Phase Circuits
|
| 3
Phase KVA = |
Volts
x Amps x 1.73
1000 |
|
| KVA |
208v |
240v |
480v |
600v |
| 3 |
8.3 |
7.2 |
3.6 |
2.9 |
| 6 |
16.6 |
14.4 |
7.2 |
5.8 |
| 9 |
25 |
21.6 |
10.8 |
8.6 |
| 15 |
41 |
36 |
18 |
14.4 |
| 22 |
62 |
54 |
27 |
21.6 |
| 30 |
83 |
72 |
36 |
28 |
| 45 |
124 |
108 |
54 |
43 |
| 75 |
208 |
180 |
90 |
72 |
| 112-1/2 |
312 |
270 |
135 |
108 |
| 150 |
416 |
360 |
180 |
144 |
| 225 |
624 |
541 |
270 |
216 |
| 300 |
832 |
721 |
360 |
268 |
| 500 |
1387 |
1202 |
601 |
481 |
| 750 |
2084 |
1806 |
903 |
723 |
| *When motor
service factor is greater than 1, increase full load amps
proportionally. Example: If service factor is 1.15, increase above amp
values by 15%. |
|