Voltage Drop
Table
|
|
Factor
x Amps x Feet |
|
|
|
Voltage
Drop = |
---------------------- |
|
|
|
|
1000 |
|
|
|
| Copper
Conductor - 90% Power Factor |
| AWG |
Single Phase |
Three Phase |
|
AWG |
Single Phase |
Three Phase |
| 14 |
.4762 |
.4167 |
|
1/0 |
.0269 |
.0231 |
| 12 |
.3125 |
.2632 |
|
2/0 |
.0222 |
.0196 |
| 10 |
.1961 |
.1677 |
|
3/0 |
.0190 |
.0163 |
| 8 |
.1250 |
.1087 |
|
4/0 |
.0161 |
.0139 |
| 6 |
.0833 |
.0714 |
|
250 |
.0147 |
.0128 |
| 4 |
.0538 |
.0463 |
|
300 |
.0131 |
.0114 |
| 3 |
.0431 |
.0379 |
|
350 |
.0121 |
.0106 |
| 2 |
.0323 |
.0278 |
|
400 |
.0115 |
.0091 |
| 1 |
.0323 |
.0278 |
|
500 |
.0101 |
.0088 |
|